BLP-LS-EE-Product-Catalog-ONLINE - Flipbook - Page 73
SPS SERIES INVERTERS
Surface Mount
Models
MINI EMERGENCY
POWER SYSTEMS
STANDARD
OPTIONAL
Recessed
Mount Models
Ceiling
T-Grid Mount Models
DESCRIPTION
OPTIONS
•
•
CEC: Certified to CEC under Title 20 regulations.
•
SDT: Self-diagnostic feature performs monthly, biannual,
and annual tests to ensure reliable operation and meet electrical
and life safety codes.
Mini-electrical inverter systems for powering up to
220W/250VA of incandescent, fluorescent, induction or LED
lighting loads. Pulse width modulated (PWM) output design
provides clean, 60Hz sinusoidal emergency power to loads.
Models are available for surface, recessed or T-Grid
mounting as required.
WARRANTY/LISTING
ELECTRICAL SPECIFICATIONS
Input
Input Voltages: 120 or 277VAC field selectable.
•
Input Frequencies: 60Hz ±2%.
•
Input Protection: AC Line Fuses.
•
Output
Output Voltages: (60Hz) 120 or 277VAC.
•
Waveform: Sinusoidal (digitally controlled, PWM design).
•
Output Frequencies: 60Hz. ±0.3Hz during emergency cycle.
•
Output Distortion: Less than 3% THD (linear load).
•
Output Protection: Line and inverter fuses.
•
•
Unit: (excluding lamps) Full coverage against defects in
materials and workmanship for 3 years from date of
shipment.
•
Battery: 3 years full warranty plus an additional 7 years of
pro-rata coverage.
•
All models are UL924 Listed and meet NFPA 101 Life Safety
Code, NEC, OSHA, Local and State Codes. Optional T-Grid
models are plenum rated, and meet City of Chicago CCEA
requirements.
•
UL listed for damp locations (20°C – 30°C).
•
FCC Part 15 Class A Compliant.
HOUSING
DIMENSIONS
•
Heavy duty steel cabinet is finished in white baked-on
powder paint providing scratch and corrosion resistance.
Standard Surface Mount Housings
•
Optional special color paint (-SP) finishes are available,
consult factory.
13 ”
11¾”
MOUNTING
Surface Mount (Standard Models): Surface mount models
are designed for mounting to walls by means of keyhole
slots provided in the back of the unit housing.
•
•
Recess Mount: (SPS-55/125, SPS-110/125 Only): Recess
models provide recess mounting holes on both sides of
the enclosure.
•
T-Grid Mount: (SPS-55/125, SPS-110/125 Only): Housing
design allows simple drop-in installation between T-grid runs.
Safety wires (supplied by others) are required for attachment
to building structure.
NOTES:
2
3
4
Available only with -125VA models.
Available only with -250VA models.
6 ”
16¾”
18 ”
4 ”
(models SPS-220/250 (models SPS-55/125
& SPS-110/250)
& SPS-110/125)
Optional Ceiling T-grid Mount Housing
4¾”
8 9/16”
8”
6 3/16”
23 ”
Sample Part Number: SPS-110/125-S-SDT
ORDERING INFORMATION
1
Optional Recessed
Mount Housing
MODEL
CAPACITY
SPS
55 Watts1
125 125VA
S Surface
SP
Special Housing color.
110 110 Watts
250 250VA
R Recessed1
SDT
Self Diagnostics
T Ceiling T-grid1
CEC Title 20 Compliant
55
220
220 Watts2
VA RATING
MOUNTING
OPTIONS
Shipped separately for field installation.
RTS
Remote Test Switch Panel 3
Not available together.
4C
4-output Circuit Switching 4
AO
Adjustable Output/Dimmer Bypass 4
740.964.1198 • BESTLIGHTING.NET • ORDERS@BESTLIGHTING.NET
73
EMERGENCY BACKUP
•